Air in a hydronic system is bad news because 1) dissolved air in the water will corrode/rust any piping or equipment made of ferrous materials and 2) free air within the piping will prevent flow, either partially or fully. Air lock within a piping system can stop flow as effectively as a closed valve. Dissolved air also hinders the heat transfer properties of water!
A common mistake we see, especially on variable speed (VFD) pumping systems, is increasing the pump speed to ensure flow at the highest point in the system. (Keep in mind, the “highest point” does not necessarily mean the “farthest point.") In one example, there was an air handling unit (AHU) on the roof of a three-story school building, located above the mechanical room. The contractor increased the pump speed to force water through the starved coil, but it did not work. The AHU still had insufficient flow, and the VFD began “hunting” (oscillating speeds). The reason it did not work was the PRV in the first floor mechanical room was set to 12-psig. For this three-story building, the vertical height to the AHU on the roof was 40-feet. So, 17.3-psig was needed to get water to the top of the system. Another 5-psig was added to ensure positive air purge pressure. The PRV setting was adjusted to 23-psig and the flow issue at the AHU disappeared.
HVAC pumps are typically meant to circulate and not boost water. So, if you are having flow issues at the top of your hydronic system, make sure the PRV has been set appropriately. Proper PRV settings at the MUW assembly, a good air separator, and venting at piping high points will help ensure proper flow and operation of your hydronic HVAC system. As always, if you need help determining what equipment you need to properly run your system, please contact your local manufacturer's representative for engineering assistance.
Last updated: March 17, 2022